Two-Wire
Continuous Level
Transmitter
INSTALLATION,
OPERATION &
MAINTENANCE MANUAL
American Magnetics, Inc.
112 Flint Road
Oak Ridge, TN 37830
Phone#: (865) 482-1056
Fax#: (865) 482-5472
www.americanmagnetics.com
[mn-175, Rev 2]
Feb 2007
MODEL 175
Page view 0
1 2 3 4 5 6 ... 17 18

Summary of Contents

Page 1 - MODEL 175

Two-Wire Continuous Level Transmitter INSTALLATION, OPERATION & MAINTENANCE MANUALAmerican Magnetics, Inc. 112 Fl

Page 2 - TABLE OF CONTENTS

10 of 18 3.) The wiring nipple is attached to the instrument enclosure at the factory (see Photo #1). The probe will normally have a coax electric

Page 3 - SECTION A

11 of 18 4.) The probe wire is the center conductor of the coax cable. Connect the Probe wire to one of the two inner terminals on the terminal block

Page 4 - Introduction

12 of 18 8.) Screw the base of the instrument enclosure onto the remote-mounting bracket. Connect conduit between the Interconnection Housing and the

Page 5 - Mounting

13 of 18 SECTION B This section contains the Operation and Maintenance instructions for the American Magnetics, Inc. Model 175 Two-Wire Continuous Le

Page 6

14 of 18 Menu Item Descriptions FUNCTION DESCRIPTION Units This is used to select the measurement units shown on the display. These units are used

Page 7 - CAUTION !

15 of 18 Menu Structure DISPLAY FUNCTION Notes 0.0 Lu 0.0 % Run Mode (Display) Level Measurement = in. or mm Level % = Percentage of loop current s

Page 8 - Installation

16 of 18 Troubleshooting General Indication Cause Solution Level, Level %, and Loop values are incorrect Poor Calibration Recalibrate using more ac

Page 9

17 of 18 Drift Test This test will determine if the transmitter or probe/application is the cause of a drifting (unstable) output. 1.) Open the ins

Page 10 - WARNING

18 of 18 Remote-mounted Units 1.) Open the interconnection housing. 2.) Disconnect the probe wiring from the terminal block. 3.) Lower the process

Page 11

2 of 18 TABLE OF CONTENTS SECTION A Foreword ...

Page 12

3 of 18 SECTION A Foreword This section contains the Installation instructions for the American Magnetics (AMI) Model 175 Two-Wire Continuous Level T

Page 13 - SECTION B

4 of 18 Photo #1 Photo #2 Instrument Housing Wiring Nipple ProbeRemote Mounting Bracket Magnet Tool Electronic Assembly (“Puck”) Interconnection Housi

Page 14 - Menu Item Descriptions

5 of 18 System Description The Model 175 liquid level system consists of the Model 175 Instrument and a CAPSEN Capacitance Probe. The instrument cons

Page 15 - Menu Structure

6 of 18 Model 175 Transmitter Dimensions – Inches Integral-mounted Transmitters Remote-mounted Transmitters 5.0″ 5.1″ 8.4″ ¾″ NPT 0.8″ 4.54″

Page 16 - Troubleshooting

7 of 18 CAUTION ! Probe (Capacitance Sensor) Model Configuration Welded fittings cannot be adjusted. Ensure the dimensions are such that when th

Page 17

8 of 18 Instrument Specifications Description Specification Power Supply 12 – 30Vdc ±10%; 24Vdc nominal Supply Voltage Effect Less than 0.01%/volt c

Page 18 - 18 of 18

9 of 18 Integral-mounted Transmitter Installation 1.) Remove the cover from the instrument enclosure. 2.) Remove the electronic assemb